The meter offers high security and detects many of the most commonly used tamper techniques. The display has large easy to read characters with information identified by OBIS. Security data can be included as part of the display sequence and read via the communication ports.
Accuracy Class 1.0 to IEC 62053-21
Communication
Mechanical
Metering Security
Unidirectional or bi-directional measurement
Full DLMS compliance
Voltage and current instrumentation values registration
communications and serial communications
Rate select for two rate meters, switch to neutral
DIN double insulated, glass filled polycarbonate case
Extensive security data
Large digit multilingual display with OBIS information indication on backlite LCD
Active and reactive energy measurement
DS1100 measures reactive energy in addition to active energy and is ideally suited for utilities who wish to bill or monitor energy consumption based on kvarh measurement. The meter offers additional instrumentation values and maximum demand as well.
DS1100 can be a simple import meter or for import/export, domestic or for net metering in solar system. An opto-isolated pulsing output can be provided as an option. The output is available via the meter auxiliary terminals.
DS1100 offers high security with various useful security features. The meter stores all registration and configuration data to nonvolatile memory. All data is retained for the life of the meter. Recordable security features are provided.
300 days of half hour data available when one channel selected, using a programmable integration
period for up to four selectable channels of load profile for any measured quantity.
DS1100 can be configured by the customer to display English characters or OBIS identification codes.
An optional battery can support the display during power outages.
DS1100 supports symmetrical and sequential connection.
Item | Description |
---|---|
Network | 1 Phase 2 Wires network |
Nominative standard | IEC 62052-11 IEC 62053-21 IEC 62053-24 IEC 62056-21 |
Accuracy class | Class 1.0 as per IEC 62053-21 Class 1.0 as per IEC 62053-24 |
Reference voltage | Un=220-240V, L-N |
Operating voltage | Range 70%-120%Un |
Basic current | Ib=5A |
Maximum current | Imax up to 80A |
Starting current | Ist=0.4%Ib |
Reference frequency | 50Hz or 60Hz +/- 5% |
Power consumption | Voltage circuit <1W, <2.5VA Current circuit < 0.25VA @ Imax |
Temperature | Operation: -40º to + 55º C Storage: -40º to + 85º C |
Enclosure | IP54 IEC 60529:1989 |
Communication | Local: Optical, RS-485 |
Item | Description |
---|---|
8 | Time-of-Use (TOU) registers |
4 | Maximum demand (MD) registers |
48 | Switching times |
4 | Seasons |
12 | Change of season dates |
32 | Exclusion dates |
12 | End of billing dates |